ACSR Technical Charcters Based on Standard BS 215 Part 2
Code Name |
Cross Section |
Stranding and Wires Dia. |
Overall Dia. |
Weight |
Rated strenth |
|||
|
AL |
ST |
Total |
AL |
ST |
mm |
Kg/km |
KN |
|
Mm2 |
mm |
||||||
Mole |
10.62 |
1.77 |
12.39 |
6/1.5 |
1/1.5 |
4.5 |
42.8 |
4.14 |
Squirrel |
20.94 |
3.49 |
24.23 |
6/2.11 |
1/2.11 |
6.33 |
84.7 |
7.87 |
Gophel |
26.24 |
4.37 |
30.62 |
6/2.36 |
1/2.36 |
7.08 |
106 |
9.58 |
Weasel |
31.61 |
5.27 |
36.88 |
6/2.59 |
1/2.59 |
7.77 |
127.6 |
11.38 |
Fox |
36.66 |
6.11 |
42.77 |
6/2.79 |
1/2.79 |
8.37 |
148.1 |
13.21 |
Ferret |
42.41 |
7.07 |
49.48 |
6/3.0 |
1/3.0 |
9.00 |
171.2 |
15.27 |
Rabbit |
52.88 |
8.81 |
61.7 |
6/3.35 |
1/3.35 |
10.1 |
213.5 |
18.42 |
Minik |
63.18 |
10.5 |
73.71 |
6/3.36 |
1/3.66 |
11 |
254.9 |
21.67 |
Skunk |
63.48 |
36.9 |
100.5 |
12/2.59 |
7/2.59 |
13 |
463 |
52.79 |
Beaver |
74.82 |
12.5 |
87.29 |
6/3.99 |
1/3.99 |
12 |
302.9 |
25.76 |
Horse |
73.37 |
42.8 |
116.2 |
12/2.79 |
7/2.79 |
14 |
537.3 |
61.26 |
Racoon |
79.20 |
13.1 |
92.4 |
6/4.09 |
1/4.09 |
12.3 |
318.3 |
27.06 |
Otter |
83.88 |
14 |
97.86 |
6/4.22 |
1/4.22 |
12.7 |
338.8 |
28.81 |
Cat |
95.40 |
15.9 |
111.3 |
6/4.5 |
1/4.5 |
13.5 |
385.3 |
32.76 |
Hare |
105 |
17.5 |
122.5 |
6/4.72 |
1/4.72 |
14.2 |
423.8 |
36.04 |
Dog |
105 |
13.6 |
118.5 |
6/4.72 |
7/4.72 |
14.2 |
394 |
32.65 |
Coyote |
131.7 |
20.1 |
151.8 |
26/2.54 |
7/1.91 |
15.9 |
520.7 |
45.86 |
Application:
Used as bare overhead transmission conductor and as primary and secondary distribution conductor and messenger support.ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
Material:
Conductor:AL1350 pure aluminum
Steel core:G1A or G2A steel wire
Zinc coating steel wire
Working Conditions:
Ambient temperature:Above -20°C
Working temperature:Not exceed 80°C
Laying bending radius:Not less than 30 times the cables outer diameter